Heating & Room Sizing
Boiler Size Calculator
Size a boiler so its net (AHRI) output matches the building's heat loss, then divide by efficiency to get the input BTU. Enter the heat loss, or estimate it from square footage and climate. The calculator gives input, gross and net ratings, boiler HP and steam lb/hr.
Boiler input size
Net output = input × efficiency × 0.87
How to Size a Boiler
- Find the building heat loss in BTU/hr (Manual J, or area × climate factor).
- Add indirect hot water load if the boiler must heat both at once.
- Match the boiler's net AHRI rating to that load. Net ≈ gross × 0.87 for hot water systems.
- Divide gross output by efficiency to get the input BTU on the nameplate.
1 boiler horsepower equals 33,475 BTU/hr of output, or 34.5 lb/hr of steam from and at 212°F.
Worked Example: 2,000 sq ft House in a Cold Climate
- Heat loss: 2,000 sq ft × 45 BTU/hr per sq ft = 90,000 BTU/hr (net load).
- Gross output: 90,000 ÷ 0.87 = 103,448 BTU/hr.
- Input: 103,448 ÷ 0.90 (90% AFUE) = 114,943 BTU/hr.
- Pick the next size up: a 120,000 BTU/hr input boiler gives 108,000 BTU/hr gross and about 93,960 BTU/hr net, which covers the 90,000 load.
Boiler Size Chart by House Size
Cold climate (45 BTU/hr per sq ft), hot water heat, 90% AFUE, no indirect water heater.
| Heated area | Heat loss (net) | Gross output | Boiler input |
|---|---|---|---|
| 1,000 sq ft | 45,000 | 51,724 | 57,471 |
| 1,500 sq ft | 67,500 | 77,586 | 86,207 |
| 2,000 sq ft | 90,000 | 103,448 | 114,943 |
| 2,500 sq ft | 112,500 | 129,310 | 143,678 |
| 3,000 sq ft | 135,000 | 155,172 | 172,414 |
| 4,000 sq ft | 180,000 | 206,897 | 229,885 |
Boiler Size FAQs
What size boiler do I need for a 2,000 sq ft house?
A 2,000 sq ft house needs about 90,000 to 110,000 BTU/hr of boiler output in a cold to very cold climate (the Heating BTU chart), or about 100,000 to 122,000 BTU/hr input at 90% efficiency.
How do I convert boiler lb/hr to BTU/hr?
Multiply steam lb/hr by about 970 BTU/lb (from and at 212°F). 1,000 lb/hr is about 970,000 BTU/hr, or 29 boiler HP.
Should I add domestic hot water to the boiler size?
Add hot water load only if the boiler also heats an indirect water tank and priority control is not used. Most systems give hot water priority, so the boiler is sized for the larger of the two loads.
What is boiler DOE heating capacity?
DOE heating capacity is the boiler's gross output in BTU/hr; net (AHRI) rating is the gross output ÷ 1.15, about 13% less (net ≈ gross × 0.87), to allow for piping and pickup. Match the net rating to your heat loss.