Heating & Room Sizing

Radiator BTU Calculator

A radiator needs about 45 to 60 watts per cubic metre of room, or 4.3 to 5.8 BTU/hr per cubic foot, at ΔT50. Enter the room and the radiator BTU calculator gives the required output, then corrects it for your system's ΔT so you choose the right radiator from its listed ΔT50 rating.

Formula with your numbers:

Heat the room needs

—
Radiator size to buy

Listed ΔT50 output needed at your system ΔT

How to Choose the Right Radiator

To choose the right radiator, calculate the room's heat loss in watts or BTU, then pick a radiator whose output at your system ΔT meets it.

  1. Measure length × width × height for the room volume.
  2. Multiply by 45 to 60 W/m³ for the room type.
  3. Adjust for single glazing, extra external walls, north-facing rooms and patio doors.
  4. Divide by the ΔT correction factor to get the ΔT50 output to look for in catalogues.
Required W = m³ × W/m³ × adjustments · ΔT50 rating = required ÷ factor

Worked example

A 4.5 × 3.5 × 2.4 m living room (37.8 m³), double glazed, 1 external wall:

37.8 × 55 = 2,079 W (7,094 BTU/hr)

On a heat pump at ΔT35 (× 0.627), choose radiators rated 3,316 W at ΔT50.

Radiator ΔT Correction Factors

Multiply a radiator's ΔT50 output by the factor to get its real output. Your ΔT is highlighted.

ΔT (°C)Factor1,000 W at ΔT50 gives
ΔT701.5481,548 W
ΔT651.4061,406 W
ΔT601.2681,268 W
ΔT5011,000 W
ΔT450.871871 W
ΔT400.747747 W
ΔT350.627627 W
ΔT300.513513 W
ΔT250.404404 W

Radiator BTU FAQs

How do I size a heated towel rail?

Size a towel rail like a bathroom radiator: about 60 W per m³ at ΔT50. Towel rails put out less than panel radiators of the same size, so if it is the only heat source, check the maker's ΔT50 output covers the room.

What does ΔT30 mean for radiator output?

ΔT30 output is about half (×0.513) of the ΔT50 catalogue rating. It applies to low-temperature systems such as heat pumps, where radiators run cooler, so they need to be about twice the size.

How many BTU does a radiator need for a room?

A living room needs about 55 W per cubic metre (about 5.3 BTU/hr per cubic foot) of radiator output at ΔT50 with double glazing. Bedrooms need about 45 W/m³.

What is ΔT50 on a radiator?

ΔT50 is the difference between the average water temperature in the radiator and the room air: a mean water temperature of 70°C (for example 75°C flow and 65°C return) in a 20°C room. Radiator outputs are published at ΔT50.

How do I convert radiator watts to BTU?

Multiply radiator watts by 3.412 to get BTU/hr. A 1,500 W radiator gives 5,118 BTU/hr.

Why do heat pump radiators need to be bigger?

Heat pumps run cooler water, often ΔT30 to ΔT35, so a radiator gives only 51% to 63% of its ΔT50 output. The radiator must be about 1.6 to 2 times larger.

Do I need more than one radiator?

Split the required output across 2 or more radiators in large rooms or rooms with several windows so heat spreads evenly.

Related Calculators

More Heating & Room Sizing Calculators

About the author

Muhammad Asim

Muhammad Asim founded The BTU Calculator. He builds every calculator, writes the pages, and checks each number against the site's shared formulas and named sources such as NIST, the U.S. EIA, ENERGY STAR and ASHRAE.

Who runs this site · How we calculate · Editorial policy · X (Twitter)