Cooling & AC
Heat Load Calculator
A cooling heat load is the sum of people (about 400 BTU/hr each), equipment and lights (watts × 3.412) and the room itself (about 20 BTU/hr per sq ft). Built for offices, server rooms, home offices and workshops where people and equipment add most of the heat.
Cooling load
BTU/hr by source
How to Calculate a Heat Load
Every watt of electricity used inside a room ends up as 3.412 BTU/hr of heat. Servers, computers, printers and lights all count. A room with no outside walls still needs cooling for its internal loads.
Worked Example: 300 sq ft Office
- People: 4 seated × 400 = 1,600 BTU/hr.
- Equipment and lights: (1,200 + 200 W) × 3.412 = 4,777 BTU/hr.
- Room envelope: 300 sq ft × 20 = 6,000 BTU/hr.
- Total: 12,377 BTU/hr, plus a 10% margin = 13,615 BTU/hr (1.13 tons). Pick the next standard size: a 15,000 BTU/hr (1.25-ton) unit.
Heat Load by Room Type
Same formula, before the safety margin.
| Room | Area · people · watts | BTU/hr |
|---|---|---|
| Home office | 150 sq ft · 1 · 300 W | 4,424 |
| Small office | 300 sq ft · 4 · 1,400 W | 12,377 |
| Meeting room | 400 sq ft · 12 · 500 W | 14,506 |
| Server closet (interior) | 50 sq ft · 0 · 2,500 W | 8,530 |
| 5 kW rack room (interior) | 100 sq ft · 0 · 5,000 W | 17,060 |
| Workshop | 600 sq ft · 3 · 3,000 W | 26,436 |
Typical equipment heat
| Equipment | Watts | BTU/hr |
|---|---|---|
| Laptop | 60 | 205 |
| Desktop PC + monitor | 300 | 1,024 |
| Laser printer (active) | 600 | 2,047 |
| Network switch | 150 | 512 |
| 1U server | 400 | 1,365 |
| Server rack (typical) | 5,000 | 17,060 |
| LED lighting per 100 sq ft | 80 | 273 |
Heat Load FAQs
How many BTU does a person give off (BTU per person)?
A seated adult gives off about 400 BTU/hr (about 250 sensible and 150 latent); a person doing light work gives off about 600 to 800 BTU/hr. This calculator uses 400 BTU/hr because it adds up the heat actually given off. ENERGY STAR room sizing adds 600 BTU/hr per extra person instead: that is a sizing allowance that also covers activity and doors opening, not a measured heat output.
How do I calculate BTU for electronic equipment?
Multiply the equipment watts by 3.412 to get BTU/hr. A 5 kW server rack releases about 17,060 BTU/hr of heat.
How do I calculate cooling for a server room?
Add equipment watts × 3.412, people × 400, lighting watts × 3.412 and the room envelope load, then add 10% to 20% margin.
What is a heat load calculation?
A heat load calculation adds every heat source in a space to find the cooling capacity needed. Sources include people, equipment, lights, sun and heat through walls.