Heating & Room Sizing
Heat Loss Calculator
Heat loss in BTU/hr is area × U-value × temperature difference for every surface, plus air leakage. Enter each surface with its R-value (or U-value for windows and doors), the design temperatures and the air change rate. The chart shows where the heat goes.
| Surface | Area (ft²) | R or U |
|---|---|---|
| Walls (net of windows) R-value | ||
| Ceiling / roof R-value | ||
| Floor R-value | ||
| Windows U-value | ||
| Doors U-value |
Typical air changes per hour: 0.35 tight new home, 0.5 average, 1.0 older home, 1.5+ drafty.
Design heat loss
BTU/hr by surface at design temperature
Heat Loss Formulas
Windows usually lose the most heat per square foot: a U-0.30 window loses about 4 times more than an R-13 wall (U-0.077). Air leakage often adds 20% to 40% of the total in older homes.
Worked Example: One Room at 70°F Inside, 10°F Outside (ΔT 60°F)
- Walls: 1,000 ft² at R-13 (U 0.077): 1,000 × 0.077 × 60 = 4,615 BTU/hr.
- Windows: 150 ft² at U-0.30: 150 × 0.30 × 60 = 2,700 BTU/hr.
- Ceiling: 1,200 ft² at R-38 (U 0.026): 1,200 × 0.026 × 60 = 1,895 BTU/hr.
- Air leakage: 9,600 ft³ at 0.5 air changes/hr: 0.018 × 9,600 × 0.5 × 60 = 5,184 BTU/hr.
- Total: 4,615 + 2,700 + 1,895 + 5,184 = 14,394 BTU/hr (4.2 kW).
Heat Loss per 100 ft² by Insulation Level
At a 60°F indoor–outdoor difference. Each row is 100 × U × 60.
| Surface | U-value | BTU/hr per 100 ft² |
|---|---|---|
| Uninsulated wall (R-4) | 0.250 | 1,500 |
| Wall R-11 | 0.091 | 545 |
| Wall R-13 | 0.077 | 462 |
| Wall R-19 | 0.053 | 316 |
| Ceiling R-30 | 0.033 | 200 |
| Ceiling R-38 | 0.026 | 158 |
| Ceiling R-49 | 0.020 | 122 |
| Single-pane window | 1.100 | 6,600 |
| Double-pane window | 0.500 | 3,000 |
| ENERGY STAR window | 0.300 | 1,800 |
Heat Loss FAQs
How do I estimate heat loss from evaporation in an open tank?
Each pound of water that evaporates carries away about 1,000 BTU. Weigh or measure how much water the tank loses per hour, multiply the pounds by about 1,000, and add that to the surface heat loss. A cover or floating balls cut it sharply.
How do I calculate BTU heat loss?
Heat loss in BTU/hr = area × U-value × temperature difference for each surface, plus air leakage loss = 0.018 × volume × air changes per hour × temperature difference. U = 1 ÷ R-value.
What is the 0.018 in the air leakage formula?
0.018 BTU/ft³·°F is the heat needed to warm 1 cubic foot of air by 1°F (0.075 lb/ft³ × 0.24 BTU/lb·°F).
What design temperature should I use?
Use your area's 99% winter design temperature: about 7°F for Boston, 23°F for Atlanta and −11°F for Minneapolis (ASHRAE Handbook—Fundamentals 99% heating design temperatures, rounded). Look up your own location in the ASHRAE climatic design data or ask your local building department.
Is this the same as a Manual J?
It uses the same physics as a Manual J heat loss, simplified to one room or one whole envelope. A full Manual J goes room by room with detailed construction tables.