Heating & Room Sizing

Heat Loss Calculator

Heat loss in BTU/hr is area × U-value × temperature difference for every surface, plus air leakage. Enter each surface with its R-value (or U-value for windows and doors), the design temperatures and the air change rate. The chart shows where the heat goes.

SurfaceArea (ft²)R or U
Walls (net of windows)
R-value
Ceiling / roof
R-value
Floor
R-value
Windows
U-value
Doors
U-value
Formula with your numbers:

Typical air changes per hour: 0.35 tight new home, 0.5 average, 1.0 older home, 1.5+ drafty.

Design heat loss

—
Where the heat goes

BTU/hr by surface at design temperature

Heat Loss Formulas

Surface loss = A × U × ΔT · U = 1 ÷ R
Air leakage loss = 0.018 × volume × ACH × ΔT

Windows usually lose the most heat per square foot: a U-0.30 window loses about 4 times more than an R-13 wall (U-0.077). Air leakage often adds 20% to 40% of the total in older homes.

Worked Example: One Room at 70°F Inside, 10°F Outside (ΔT 60°F)

  1. Walls: 1,000 ft² at R-13 (U 0.077): 1,000 × 0.077 × 60 = 4,615 BTU/hr.
  2. Windows: 150 ft² at U-0.30: 150 × 0.30 × 60 = 2,700 BTU/hr.
  3. Ceiling: 1,200 ft² at R-38 (U 0.026): 1,200 × 0.026 × 60 = 1,895 BTU/hr.
  4. Air leakage: 9,600 ft³ at 0.5 air changes/hr: 0.018 × 9,600 × 0.5 × 60 = 5,184 BTU/hr.
  5. Total: 4,615 + 2,700 + 1,895 + 5,184 = 14,394 BTU/hr (4.2 kW).

Heat Loss per 100 ft² by Insulation Level

At a 60°F indoor–outdoor difference. Each row is 100 × U × 60.

SurfaceU-valueBTU/hr per 100 ft²
Uninsulated wall (R-4)0.2501,500
Wall R-110.091545
Wall R-130.077462
Wall R-190.053316
Ceiling R-300.033200
Ceiling R-380.026158
Ceiling R-490.020122
Single-pane window1.1006,600
Double-pane window0.5003,000
ENERGY STAR window0.3001,800

Heat Loss FAQs

How do I estimate heat loss from evaporation in an open tank?

Each pound of water that evaporates carries away about 1,000 BTU. Weigh or measure how much water the tank loses per hour, multiply the pounds by about 1,000, and add that to the surface heat loss. A cover or floating balls cut it sharply.

How do I calculate BTU heat loss?

Heat loss in BTU/hr = area × U-value × temperature difference for each surface, plus air leakage loss = 0.018 × volume × air changes per hour × temperature difference. U = 1 ÷ R-value.

What is the 0.018 in the air leakage formula?

0.018 BTU/ft³·°F is the heat needed to warm 1 cubic foot of air by 1°F (0.075 lb/ft³ × 0.24 BTU/lb·°F).

What design temperature should I use?

Use your area's 99% winter design temperature: about 7°F for Boston, 23°F for Atlanta and −11°F for Minneapolis (ASHRAE Handbook—Fundamentals 99% heating design temperatures, rounded). Look up your own location in the ASHRAE climatic design data or ask your local building department.

Is this the same as a Manual J?

It uses the same physics as a Manual J heat loss, simplified to one room or one whole envelope. A full Manual J goes room by room with detailed construction tables.

Related Calculators

More Heating & Room Sizing Calculators

About the author

Muhammad Asim

Muhammad Asim founded The BTU Calculator. He builds every calculator, writes the pages, and checks each number against the site's shared formulas and named sources such as NIST, the U.S. EIA, ENERGY STAR and ASHRAE.

Who runs this site · How we calculate · Editorial policy · X (Twitter)