Gas & Fuel

Gas Pipe Sizing Calculator

Divide the total BTU/hr by 1,036 to get CFH, then pick the smallest pipe whose capacity at the longest run length is at least that CFH. Enter the total gas load and the longest pipe run. The calculator picks the Schedule 40 steel pipe size for natural gas at under 2 psi with a 0.5 in w.c. pressure drop.

Formula with your numbers:

For planning only. Gas piping must follow your local code and be installed and pressure-tested by a licensed professional. Tables differ for CSST, copper, propane and higher pressures.

Pipe size

—
Pipe capacity at your run length

CFH vs your load

Natural Gas Pipe Sizing Chart (CFH)

Schedule 40 metallic pipe, natural gas (0.60 SG), inlet under 2 psi, 0.5 in w.c. pressure drop. 1 CFH ≈ 1,036 BTU/hr.

Length½"¾"1"1¼"1½"2"
10 ft1723606781,3902,0904,020
20 ft1182474669571,4302,760
30 ft951993747681,1502,220
40 ft811703206579851,900
50 ft721512845838731,680
60 ft651372575287911,520
70 ft601262374867281,400
80 ft561172204526771,300
90 ft521102074246351,220
100 ft501041954006001,160

Gas Pipe Sizing FAQs

How do I clock a gas meter to find an appliance's BTU?

Turn off every other gas appliance, time one full turn of the meter's test dial, then use BTU/hr = 3,600 ÷ seconds × dial size (ft³) × 1,036. If a 1 ft³ dial takes 90 seconds, the appliance uses 3,600 ÷ 90 × 1,036 ≈ 41,400 BTU/hr.

How many BTU can a 1 inch gas line carry?

A 1" Schedule 40 natural gas line carries about 678 CFH (≈702,000 BTU/hr) at 10 ft, 284 CFH (≈294,000 BTU/hr) at 50 ft and 195 CFH (≈202,000 BTU/hr) at 100 ft (under 2 psi, 0.5 in w.c. drop).

Is black iron gas pipe the same as Schedule 40?

Yes. Black iron gas pipe is Schedule 40 steel pipe, so this table applies to it. CSST, copper and polyethylene pipe use different tables.

Can I convert a natural gas appliance to propane?

Only with the maker's conversion kit, installed by a qualified gas technician. Propane holds about 2,500 BTU per cubic foot versus about 1,036 for natural gas, so it needs smaller orifices and a different regulator setting.

What size gas line do I need for 100,000 BTU?

100,000 BTU/hr is about 97 CFH of natural gas. A ½" pipe carries it up to about 20 ft (118 CFH). For runs of 30 to 100 ft use ¾" pipe (199 CFH at 30 ft, 104 CFH at 100 ft).

How far can you run a ½ inch gas line?

A ½" Schedule 40 line carries 172 CFH at 10 ft but only 72 CFH at 50 ft and 50 CFH at 100 ft (natural gas, 0.5 in w.c. drop).

How many BTU can a ¾ inch gas line carry?

A ¾" line carries about 373,000 BTU/hr at 10 ft, 206,000 at 30 ft and 108,000 at 100 ft of natural gas.

Which length do I use for gas pipe sizing?

Use the longest run from the meter to the farthest appliance, and size every section with that length for the load it carries (the longest-length method in NFPA 54 / IFGC).

Related Calculators

More Gas & Fuel Calculators

About the author

Muhammad Asim

Muhammad Asim founded The BTU Calculator. He builds every calculator, writes the pages, and checks each number against the site's shared formulas and named sources such as NIST, the U.S. EIA, ENERGY STAR and ASHRAE.

Who runs this site · How we calculate · Editorial policy · X (Twitter)