Every tool on this site uses one shared set of formulas and constants. They are listed here, with sources, so you can check any result by hand.

Published 24 Nov 2026

The BTU we use

All tools use the International Table BTU (BTUIT): 1 BTU = 1,055.05585262 joules, as listed in NIST Special Publication 811. It is roughly the heat needed to warm 1 pound of water by 1°F.

We keep two kinds of quantity apart:

  • Energy (BTU): an amount of heat, like kWh, joules or therms.
  • Power (BTU/hr): a rate of heat flow, like watts, kW, horsepower or tons of refrigeration. Air conditioners and heaters are rated in BTU/hr, even when labels just say "BTU".

Energy = power × time. A 10,000 BTU/hr heater running 3 hours delivers 30,000 BTU.

Power conversions (to BTU/hr)

1 unit ofBTU/hr
Watts (W)3.412142
Kilowatts (kW)3,412.142
Horsepower (HP)2,544.43
Tons of refrigeration12,000
MBH (1,000 BTU/hr)1,000
BTU per second (BTU/s)3,600

1 ton of refrigeration = 12,000 BTU/hr (the heat to melt 1 short ton of ice in 24 hours). Horsepower is mechanical horsepower (745.7 W). Boiler horsepower (33,475 BTU/hr) is a different unit with its own page.

Energy conversions (to BTU)

1 unit ofBTU
Kilowatt-hours (kWh)3,412.142
Watt-hours (Wh)3.412142
Joules (J)0.000947817
Kilojoules (kJ)0.947817
Kilocalories (kcal)3.96567
Calories (cal)0.00396567
Foot-pounds force (ft·lbf)0.001285067
MBtu (1,000 BTU)1,000
Therms100,000
MMBtu1,000,000

Calories are thermochemical (1 cal = 4.184 J); 1 kcal equals 1 food Calorie.

Fuel heat content

Fuel figures are typical higher heating values from the U.S. Energy Information Administration (EIA). Actual gas heat content varies by supplier, usually 1,000 to 1,100 BTU per cubic foot; your gas bill shows the local value.

FuelBTU
Natural gas, cubic feet1,036
Natural gas, CCF103,600
Natural gas, MCF1,036,000
Therms100,000
Propane, gallons91,452
Heating oil, gallons138,500
MMBtu1,000,000
Propane, pound21,600
Firewood, cord (species dependent)14.3 to 27.7 million

Delivered heat = fuel BTU × appliance efficiency (AFUE for furnaces and boilers). Cost per million BTU = price per unit ÷ (BTU per unit × efficiency) × 1,000,000.

Air conditioner sizing

Room AC sizes start from the ENERGY STAR room air conditioner chart:

Area (sq ft)BTU/hr
100 to 1505,000
150 to 2506,000
250 to 3007,000
300 to 3508,000
350 to 4009,000
400 to 45010,000
450 to 55012,000
550 to 70014,000
700 to 1,00018,000
1,000 to 1,20021,000
1,200 to 1,40023,000
1,400 to 1,50024,000
1,500 to 2,00030,000
2,000 to 2,50034,000

ENERGY STAR adjustments: reduce 10% for a heavily shaded room, add 10% for a very sunny room, add 600 BTU/hr per person over two, and add 4,000 BTU/hr for a kitchen. Ceiling height above 8 ft scales the result proportionally. Portable AC results are compared against the DOE SACC rating, which is typically 25 to 40% lower than the ASHRAE rating on the box.

Heating sizing

  • By area: BTU/hr = sq ft × climate factor (about 30 in hot climates to 60 in very cold ones) × insulation multiplier × (ceiling height ÷ 8).
  • By volume (garage and workshop): BTU/hr = cubic feet × temperature rise (°F) × 0.133, × 0.8 for good insulation or × 1.3 for none. This is a rule of thumb.
  • Equipment input: furnace or boiler input = heat needed ÷ AFUE.
  • Heat loss: BTU/hr = U-value × area × ΔT for each wall, window, roof and floor, plus air leakage = 0.018 × volume × air changes per hour × ΔT.
  • Greenhouse: BTU/hr = covering area × U-value × ΔT × wind factor (1.0 to 1.25).
  • Pool: BTU/hr to hold temperature = surface area × (water − air temperature) × 12 (U.S. DOE rule of thumb).

These are planning estimates. Final equipment sizing should come from an ACCA Manual J load calculation and Manual S equipment selection by a licensed contractor.

Water and air heat transfer

  • Water: BTU = gallons × 8.34 × ΔT (°F). For flow, BTU/hr = 500 × GPM × ΔT. Glycol mixes use a lower factor (470 for 30%, 450 for 50%).
  • Air: BTU/hr = 1.08 × CFM × ΔT (sensible heat at standard air density).
  • Any material: Q = mass × specific heat × ΔT.

Electrical

Electric heat: watts = BTU/hr ÷ 3.412142. Air conditioners: watts = BTU/hr ÷ EER, then amps = watts ÷ volts. Circuits are sized so running amps stay at or below 80% of the breaker rating; the nameplate's maximum breaker size always takes priority.

Gas flow and pipe sizing

CFH = BTU/hr ÷ 1,036 for natural gas. Pipe sizes come from the International Fuel Gas Code (IFGC) Table 402.4(2) for Schedule 40 metallic pipe, natural gas, inlet under 2 psi and a 0.5 in w.c. pressure drop, using the longest-length method. Gas piping must follow your local code and be installed and tested by a licensed professional.

Rounding

Results are rounded for reading (for example to the nearest 100 BTU/hr), but the full value is used in all further steps. Equipment recommendations round up to the next standard size.

Limits of these estimates

Results are estimates for planning and comparison. They do not replace a professional load calculation, a gas fitter's design or the equipment maker's installation instructions. Spotted something wrong? Tell us.