Heating & Room Sizing
Radiant Floor Heating BTU Calculator
A radiant floor must supply the room's heat loss divided by the heated floor area, usually 15 to 35 BTU/hr per square foot. Enter the room heat loss and floor area to see the BTU per sq ft, the floor surface temperature it needs, the PEX length and the flow in GPM.
Floor output needed
Comfort limit about 85°F (29°C)
How Radiant Floor Output Works
A heated floor gives off about 2 BTU/hr per sq ft for each °F the surface is warmer than the room. So 30 BTU/hr per sq ft needs a floor about 15°F above room temperature.
Floor coverings with a higher R-value need hotter water for the same output; thick carpet can push supply water above 130°F.
Radiant Floor FAQs
Is radiant floor heating the same as underfloor heating?
Yes. Radiant floor heating and underfloor heating are the same thing: warm water pipes (or electric mats) under the floor that heat the room from below. This calculator works for both names.
How many BTU per square foot does radiant floor heating give?
Radiant floors deliver about 15 to 35 BTU/hr per square foot, limited by a comfortable floor surface of about 85°F (29°C).
What floor surface temperature is safe?
Keep living area floors at or below about 85°F (29°C); bathrooms and perimeter zones can run near 90°F.
How much PEX tubing do I need?
Tubing length ≈ area × 12 ÷ spacing in inches. At 12-inch spacing, use about 1 ft of tube per sq ft; at 6-inch spacing, 2 ft per sq ft.
What if the room needs more than the floor can give?
Add supplemental heat (a panel radiator or baseboard) or improve insulation when the load per sq ft exceeds about 35 BTU/hr.