Heating & Room Sizing

BTU to GPM Calculator

To convert BTU per hour to gallons per minute, divide the BTU/hr by 500 times the temperature difference in °F. A 100,000 BTU/hr boiler with a 20°F temperature drop needs 10 GPM of water. Switch direction to convert GPM to BTU.

Fluid
Formula with your numbers:

Flow needed

—
Which copper pipe carries this flow?

Typical max GPM at about 4 ft/s

BTU to GPM Formula

The hydronic heat formula is BTU/hr = 500 × GPM × ΔT.

GPM = BTU/hr ÷ (500 × ΔT) · BTU/hr = 500 × GPM × ΔT
  1. Find the boiler output or zone heat loss in BTU/hr.
  2. Choose the design temperature drop: 20°F for most boilers, 10°F for chilled water, 30 to 40°F for low-flow systems.
  3. Divide BTU/hr by 500 × ΔT.

Worked example

A 60,000 BTU/hr radiant zone at a 20°F drop:

60,000 ÷ (500 × 20) = 6 GPM

That flow fits ¾-inch copper (about 4 GPM) only at higher velocity, so 1-inch is the safer choice.

BTU to GPM Chart (Water)

BTU/hrΔT 10°FΔT 20°FΔT 30°FΔT 40°F
20,000421.31
40,000842.72
60,00012643
80,0001685.34
100,00020106.75
150,0003015107.5
200,000402013.310
300,00060302015
500,0001005033.325
1,000,00020010066.750

BTU to GPM FAQs

How many GPM per BTU?

At a 20°F temperature drop, 1 GPM of water carries 10,000 BTU/hr. GPM = BTU/hr ÷ (500 × ΔT).

Where does the 500 in the GPM formula come from?

500 = 8.33 lb per gallon × 60 minutes per hour × 1 BTU/lb·°F for water.

How do I convert GPM to BTU?

To convert GPM to BTU/hr, multiply GPM × 500 × temperature difference in °F. 5 GPM at a 20°F drop is 50,000 BTU/hr.

What GPM does a 100,000 BTU boiler need?

A 100,000 BTU/hr boiler needs 10 GPM at a 20°F temperature drop, or 5 GPM at a 40°F drop.

How does glycol change the GPM?

Glycol mixes carry less heat per gallon, so they need about 5% to 15% more flow than water. The calculator uses factors of 470 (30% glycol) and 450 (50% glycol).

Related Calculators

More Heating & Room Sizing Calculators

About the author

Muhammad Asim

Muhammad Asim founded The BTU Calculator. He builds every calculator, writes the pages, and checks each number against the site's shared formulas and named sources such as NIST, the U.S. EIA, ENERGY STAR and ASHRAE.

Who runs this site · How we calculate · Editorial policy · X (Twitter)