BTU to CFM Calculator
To convert BTU per hour to CFM, divide the BTU/hr by 1.08 times the temperature difference in °F. A 24,000 BTU/hr air conditioner with a 20°F supply-air difference needs 1,111 CFM. Switch direction to convert CFM to BTU.
1.08 applies to standard air at sea level. At 5,000 ft (1,520 m) use about 0.90.
Airflow needed
Formula result vs the 350–400 CFM per ton rule
BTU to CFM Formula
The sensible heat formula links BTU, airflow and temperature: BTU/hr = 1.08 × CFM × ΔT.
- Find the heat load or equipment output in BTU/hr.
- Find the temperature difference: supply air minus room air (heating) or room air minus supply air (cooling).
- Divide BTU/hr by 1.08 × ΔT.
The sensible formula covers temperature change only. Air conditioners also remove moisture (latent heat), so cooling design uses the 350 to 400 CFM per ton rule.
Worked example
An 80,000 BTU/hr output furnace with a 55°F temperature rise:
80,000 ÷ (1.08 × 55) = 1,347 CFM
A 3-ton (36,000 BTU/hr) air conditioner at 400 CFM per ton needs 1,200 CFM.
BTU to CFM Chart
CFM for each heat load at common temperature differences. Your row and ΔT column are highlighted.
| BTU/hr | ΔT 15°F | ΔT 20°F | ΔT 25°F | ΔT 30°F | ΔT 40°F | ΔT 50°F | 400 CFM/ton |
|---|---|---|---|---|---|---|---|
| 6,000 | 370 | 278 | 222 | 185 | 139 | 111 | 200 |
| 12,000 | 741 | 556 | 444 | 370 | 278 | 222 | 400 |
| 18,000 | 1,111 | 833 | 667 | 556 | 417 | 333 | 600 |
| 24,000 | 1,481 | 1,111 | 889 | 741 | 556 | 444 | 800 |
| 30,000 | 1,852 | 1,389 | 1,111 | 926 | 694 | 556 | 1,000 |
| 36,000 | 2,222 | 1,667 | 1,333 | 1,111 | 833 | 667 | 1,200 |
| 42,000 | 2,593 | 1,944 | 1,556 | 1,296 | 972 | 778 | 1,400 |
| 48,000 | 2,963 | 2,222 | 1,778 | 1,481 | 1,111 | 889 | 1,600 |
| 60,000 | 3,704 | 2,778 | 2,222 | 1,852 | 1,389 | 1,111 | 2,000 |
| 80,000 | 4,938 | 3,704 | 2,963 | 2,469 | 1,852 | 1,481 | 2,667 |
| 100,000 | 6,173 | 4,630 | 3,704 | 3,086 | 2,315 | 1,852 | 3,333 |
BTU to CFM FAQs
Can I use SCFM in the BTU to CFM formula?
Yes. The 1.08 factor assumes standard air (0.075 lb/ft³), which is exactly what SCFM measures. At high altitude, actual CFM is higher than SCFM for the same BTU.
How many CFM per ton of cooling?
Air conditioners move about 350 to 400 CFM per ton of cooling. 400 CFM per ton is the standard design value; humid climates use 350.
How many CFM do I need for 24,000 BTU?
A 24,000 BTU/hr (2-ton) air conditioner needs about 800 CFM at 400 CFM per ton, or 1,111 CFM at a 20°F temperature difference.
Where does the 1.08 in the CFM formula come from?
The 1.08 factor is 0.075 lb/ft³ (air density) × 60 min/hr × 0.24 BTU/lb·°F (specific heat of air). It applies to standard air at sea level.
How do I convert CFM to BTU?
To convert CFM to BTU/hr, multiply CFM × 1.08 × temperature difference in °F. 1,000 CFM at a 20°F difference carries 21,600 BTU/hr.
What temperature rise should a furnace have?
Most gas furnaces are designed for a 30°F to 70°F temperature rise across the heat exchanger. The exact range is on the furnace nameplate.