Heating & Room Sizing
Garage Heater BTU Calculator
A garage heater needs about cubic feet × temperature rise (°F) × 0.133 BTU per hour with average insulation. A 24 × 24 ft 2-car garage with 8 ft ceilings needs about 24,500 BTU/hr to warm 40°F. Uninsulated garages need about 30% more.
Heater size needed
Plan to scale · heater sizes vs your load
How to Size a Garage Heater
To size a garage heater, multiply the garage volume by the temperature rise and by an insulation factor.
- Measure length, width and ceiling height in feet and multiply for cubic feet.
- Subtract the coldest outdoor temperature from the temperature you want.
- Multiply cubic feet × ΔT × 0.133 (average), × 1.3 for no insulation or × 0.8 for good insulation.
- Pick the next heater size up.
Worked example
A 24 × 24 ft garage, 8 ft ceiling, 20°F outside, 60°F target, average insulation:
4,608 ft³ × 40 × 0.133 = 24,515 BTU/hr
A 30,000 BTU/hr heater fits; an electric heater needs 7.2 kW.
Garage Heater Size Chart
BTU/hr for 8 ft ceilings and average insulation.
| Garage | Size (ft) | ft³ | ΔT 30°F | ΔT 40°F | ΔT 50°F | ΔT 60°F |
|---|---|---|---|---|---|---|
| 1-car | 12 × 22 | 2,112 | 8,427 | 11,236 | 14,045 | 16,854 |
| 1.5-car | 16 × 24 | 3,072 | 12,257 | 16,343 | 20,429 | 24,515 |
| 2-car | 24 × 24 | 4,608 | 18,386 | 24,515 | 30,643 | 36,772 |
| 2.5-car | 28 × 24 | 5,376 | 21,450 | 28,600 | 35,750 | 42,900 |
| 3-car | 32 × 24 | 6,144 | 24,515 | 32,686 | 40,858 | 49,029 |
| Large shop | 40 × 30 | 9,600 | 38,304 | 51,072 | 63,840 | 76,608 |
Gas, Propane or Electric Garage Heaters
There are 3 main garage heater types:
- Electric (240 V) heaters run 4,000 to 10,000 W (13,600 to 34,100 BTU/hr) and need no venting.
- Natural gas or propane unit heaters (vented) run 30,000 to 125,000 BTU/hr and suit large or poorly insulated garages.
- Infrared tube heaters warm objects and people directly and suit tall ceilings and shops with open doors.
Garage Heater BTU FAQs
How many BTU do I need to heat a 2-car garage?
A 24 × 24 ft 2-car garage with 8 ft ceilings needs about 25,000 BTU/hr to warm 40°F with average insulation, and about 32,000 BTU/hr if the garage is uninsulated.
How many BTU to heat a 24x24 garage?
A 24 × 24 ft garage (4,608 ft³ at 8 ft) needs about 24,500 BTU/hr for a 40°F rise with average insulation, and about 36,800 BTU/hr for a 60°F rise.
What is the garage heater BTU formula?
Garage heater BTU/hr = cubic feet × temperature rise (°F) × 0.133 for average insulation. Use a higher factor for an uninsulated garage.
How many kW electric heater for a garage?
Divide the BTU/hr by 3,412 to get kW. A 24,500 BTU/hr load needs a 7.5 kW (240 V) electric garage heater.
Can I use a propane heater in a closed garage?
Only use a heater rated for indoor use, keep ventilation open and run a carbon monoxide alarm. Unvented propane and kerosene heaters release combustion gases into the space.